| INPUT | |
|---|---|
| Phases | 1 |
| Nominal input voltage | 100 to 240 VAC |
| Input voltage range | 85 to 264 VAC; 120 to 372 VDC |
| Input voltage derating | -2.5 %/V (< 95 VAC) |
| Input current | ≤ 0.97 A (240 VAC); ≤ 1.84 A (100 VAC) |
| Discharge current | ≤ 1 mA |
| Inrush current | ≤ 30 A |
| Power factor correction (PFC) | Passive |
| Mains failure hold-up time | ≥ 80 ms (230 VAC); ≥ 15 ms (100 VAC) |
| OUTPUT | |
|---|---|
| Nominal output voltage | 48 VDC (SELV) |
| Output voltage range | 40 to 53 VDC (adjustable) |
| Factory preset | 48 VDC |
| Nominal output current | 2 A (48 VDC); 2.1 A (< 40 °C) |
| Nominal output power | 96 W |
| SIGNALING AND COMMUNICATION | |
|---|---|
| Signaling | 1 x LED DC OK (green); 1 x active signal output DC OK (48 VDC, 10 mA) |
| Operation status indicator | LED green |
| EFFICIENCY | |
|---|---|
| Power loss | ≤ 1W (230 VAC; no load); ≤ 16.2W (230 VAC; nominal load) |
| Max. power loss | ≤ 19.8W (100 VAC / 48 VDC; 2 A) |
| Efficiency | ≥86% |
| FUSE PROTECTION | |
|---|---|
| Internal fuse | T 4 A / 250 VAC |
| External fuse (required) | External DC fuse required for DC input voltage |
| External fuse (recommended) | Circuit breakers 6 A, 10 A, 16 A, characteristic: B or C an external DC fuse required for DC input voltage |
| GENERAL | |
|---|---|
| Dimensions (WxHxL) | 52mmx90mmx119mm |
| Weight | 410 g |
| Type of mounting | DIN-35 rail |
| Protection class | II |
| Degree of protection | IP20 |
| ENVIRONMENTAL | |
|---|---|
| Operating Temperature | -25 to 70 °C |
| Storage Temperature | -25 to 85 °C |
| Relative humidity | 5-96 % (no condensation permissible) |
| Derating | -3 %/K (> 50 °C) |
| STANDARDS | |
|---|---|
| Conformity marking | CE |
| Standards/specifications | EN 60950-1; EN 61204-3; EN 60335-1; UL 60950-1; UL 508; GL |